Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/28/2002 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 10/26/2002 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*DATA PLATES STILL NOT MARKED ON HEAT PUMPS. RAISE SEWER VENTS 2' ABOVE AIR INTAKES ON UNITS #6 & 7. RECALL FOR FINISH. |
| 10/16/2002 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) ALL UNITS ON ROOF ARE REQUIRED TO HAVE OUTSIDE AIR VENTS. 2.) PROVIDE SUN SHIELD OVER CANVAS CONNECTORS. 3.) BLOCK & CLAMP PVC ON ROOF EVERY 4' PAINT W/LATEX PAINT. 4.) PERMANENTLY LABEL UNITS ON ROOF. NO INK 5.) MARK DATA PLATES ON HEAT PUMPS W/PROPER HEAT KIT INSTALLED & FUSE UNITS ACCORDINGLY. RECALL FOR FINAL. |