Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T02CM02857
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/28/2002 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000* | |
10/26/2002 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*DATA PLATES STILL NOT MARKED ON HEAT PUMPS. RAISE SEWER VENTS 2' ABOVE AIR INTAKES ON UNITS #6 & 7. RECALL FOR FINISH. | |
10/16/2002 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*1.) ALL UNITS ON ROOF ARE REQUIRED TO HAVE OUTSIDE AIR VENTS. 2.) PROVIDE SUN SHIELD OVER CANVAS CONNECTORS. 3.) BLOCK & CLAMP PVC ON ROOF EVERY 4' PAINT W/LATEX PAINT. 4.) PERMANENTLY LABEL UNITS ON ROOF. NO INK 5.) MARK DATA PLATES ON HEAT PUMPS W/PROPER HEAT KIT INSTALLED & FUSE UNITS ACCORDINGLY. RECALL FOR FINAL. |