Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T02CM02854
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/07/2003 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
04/04/2003 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0245* 1.) EMT CONDUIT TO BE SUPPORTED WITHIN 3' OF TERMINATION. 2.) MC CABLE TO BE SUPPORTED WITHIN 12" EACH TERMINATION, AND USE LISTED STRAPS. SEE ARTS 110-3, 334-10 '99NEC. 3.) INSTALL NAIL PLATES ON STUDS WHERE MC CABLE NOT 1 1/4" BACK FROM OUTSIDE FACE OF STUD. SEE ART 300-4 NEC. |