Permit: T02CM02851

Parcel: 14016003F

Inspection Status: Approved

Inspection History: PLUMBING - SEWER HCS CONNECT

Permit Number - T02CM02851

Inspection Description - PLUMBING - SEWER HCS CONNECT

Inspection Status - Approved

Date Description Inspector Results Comments
06/11/2003 PLUMBING - SEWER HCS CONNECT Approved IVRS - Inspection 0000*/ 1) PLUMBING FINAL IS OK 2) HCS CONNECTION IS OK 3) OK FOR TEMP C OF O
06/10/2003 PLUMBING - SEWER HCS CONNECT Partial Approval 1) AIR PRESSURE TEST IS OK FOR M.H. # 1, 2, AND 3 IS OK
06/09/2003 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection 0000*/ 1) 8" SITE SEWER DUCTILE, RUN IS OK FROM M.H. #3 WEST TO C.O. IS OK 2) OK TO BACKFILL TRENCH
06/06/2003 PLUMBING - SEWER HCS CONNECT Not ready for Inspection IVRS - Inspection 0000*/ 1) NOT READY FOR INSPECTION
06/05/2003 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection 0000*/ 1) 8" SITE FENCE FROM M.H.#2 NORTH TO M.H. #3 2) BASES HAVE BEEN SET FOR M.H. 1 & 2 3) OK FOR BACKFILL
06/03/2003 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection 0000*/ 1) 8" SITE SEWER IS OK FROM M.H. #1 WEST TO 20' EAST OF PRIVATE M.H. #2 IS OK 2) OK TO BACKFILL TRENCH 3) WILL VERIFY AIR PRESSURE TEST AT A LATER TIME 4) WILL REQUIRE A REVISED AND APPROVED PLAN ON SITE SEWER BY FINAL SEWER INSPECTION