Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/19/2002 |
PLUMBING - ROUGH, SOIL |
|
Approved |
IVRS - Inspection 0000* |
| 11/15/2002 |
PLUMBING - ROUGH, SOIL |
|
Denied |
IVRS - Inspection 0999*/ 1) 10' HIGH MINIMUM TEST REQUIRED ON ABS SOIL PLUMBING 2) PREVIOUSLY ADVISED ON LAST INSPECTION |
| 11/14/2002 |
PLUMBING - ROUGH, SOIL |
|
Denied |
IVRS - Inspection 0999*/ 1) CLEANOUTS ARE INSTALLED INCORRECTLY-REVERSED 2) ROUGH PLUMBING TO SHALLOW MUST BE 12" BELOW GRADE TO TOP OF PLUMBING 3) PLUMBING MUST BE CONTINOUSLY SUPPORTED OR UNDISTURBED OR COMPACTED SOIL 4) YOU MUST PERFORM A 10 FOOT WATER TEST PER UPC SECTION 712.2 5) NO PLANS PERMITS ON SITE |