Inspection Status: Closed
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/21/2007 |
ELECTRIC - FINAL |
|
Closed |
|
| 12/21/2007 |
ELECTRIC - FINAL |
|
Approved |
Last outstanding issue was derating for multiple conductors in a conduit. Field verified code compliance. |
| 08/21/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*PLEASE VERIFY DERATING FOR MUTIPILE CIRCUITS CONDUITS 310-15. 6 CIRCUITS |
| 08/20/2002 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*1.) PLEASE CLEAN EXCESSIVE PAINT FROM RECEPTACLES 2.) VERIFY DERATING FOR CIRCUITS IN CONDUITS 310-15. 3.) FINISH INSTALLATION OF SWITCHES AND RECEPTACLES 4.) BOND JUNCTION BOX ENCLOUSER. |
| 08/05/2002 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*PLEASE FINISH ALL RUNS IN HARD CEILING. TIGHTEN FITTINGS AT LAST RECEPTICAL BOX. |