Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 01/03/2003 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 12/27/2002 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*/ 1) UNDER SIZE WIRING AT RANGE (50A REQUIRES #6) 2) UNDERSIZE WIRING AT A/C CONDENSOR (35A REQUIRES #8) 4) WATER TEST IS REQUIRED ON DWV SYSTEM 5) INSTALL TUB/SHOWER VALVES |
| 12/26/2002 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999* HOUSE LOCKED/NO ACCESS |
| 11/22/2002 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*/ 1) PLAN CALLS FOR GALVANIZED DUCT WORK FLEX USED-BUILD TO PLAN OR HAVE PLAN REVISED AND APPROVED FOR FLEX NO INSPECTION 2) OUTSIDE GFCI'S CANNOT BE ON BATHROOM CIRCUITS 3) KITCHEN COUNTER OUTLETS MUST BE ON 2 SEPARATE 20 AMP CIRCUITS WITH NO OTHER OUTLETS ON THOSE CIRCUITS 4) NAIL PROTECT ALL WIRES WITHIN 1 1/4" OF STUD SURFACE 5) STOPPED INSPECTION HOUSE NOT PER PLAN OR CODE |