Permit: T02CM02772

Parcel: 107051010


Addresses:

472 W LAGUNA ST 02

Inspection Status: Approved

Inspection History: ELECTRIC - TEMPORARY POLE

Date Description Inspector Results Comments
02/10/2003 ELECTRIC - TEMPORARY POLE Approved
10/09/2002 ELECTRIC - TEMPORARY POLE Partial Approval IVRS - Inspection 0000*SENT TO TEP 10/9/02 AT 9:15AM.OK TEMP POLE 1.) PROVIDE A BARRIAR TO PROTECT PVC RUN TO TRAILER.
10/07/2002 ELECTRIC - TEMPORARY POLE Partial Approval IVRS - Inspection 0000*1.)SECURE BACK BOARD TO POLE 2.) LABEL BREAKERS 3.) USE AN APPROVED FITTING TO CONNECT BELL BOX. 4.) TIGHTEN ALL CONDUCTOR TERMANANTIONS. PLEASE HAVE UNDERGROUND ELECTRIC ADDED TO PERMIT.