Permit: T02CM02772

Parcel: 107051010


Addresses:

472 W LAGUNA ST 02

Inspection Status: Denied

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
01/09/2003 ELECTRIC - CABLE DROP Denied IVRS - Inspection 0999*
01/09/2003 ELECTRIC - CABLE DROP Approved IVRS - Inspection 0000*APPROVED OK TO CLEAR CABLE DROP.
1.) SERVICE ADDRESSED WRONG SAYS 742 W. LAGUNA 4,5,6 SHOULD BE 472 W LAGUNA STRUCTURE #2 AS ON PERMIT.
2.) NOTE FOR POWER CLEARENCE ID MAIN DISCONNECTS.
01/07/2003 ELECTRIC - CABLE DROP Not ready for Inspection IVRS - Inspection 0000*
1.) ADDRESS SERVICE
2.) INSTALL GROUNDING BUSHING ON 4" NIPPLE INSIDE GUTTER 250-94 STANDARD LN'S NOT APPROVED.
3.) MAIN BONDING JUMPER FROM GROUNDING ELECTRODE CONDUCTOR TO NEUTRAL.
12/30/2002 ELECTRIC - CABLE DROP Not ready for Inspection IVRS - Inspection 0000*FINISH WIRING TO TOP OF METER SCOCKETS.