Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/17/2002 |
BUILDING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 10/14/2002 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0950*/ 1) NO POWER GARAGE WEST OUTLET 2) NO POWER TO WATER HEATER 3) NO POWER TO KITCHEN GFCI'S 4) NO STUCCO CERTIFICATE 4) STOPPED INSPECTION |