Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 09/13/2002 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 09/10/2002 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) H2.5 CLIPS MUST BE NAILED WITH 5-8D NAILS THRU WEB STIFFNERS ON BOTH SIDES OF TJI JOISTS NOT INTO WEB OR LAMINATED CHORD WITHOUT STIFFNERS 2) PROVIDE TJI ENGINEER EVALUATION OF ALL SPLIT CHORD TJI 3) HEADER MISSING AT MASTER BEDROOM 4) INTERIOR BEARING WALL NOT PROPERLY ANCHORED 5) ITEMS FROM 7/25/02 NOT COMPLIED WITH REPEAT REFEE 6) LIVING ROOM WALL NOT ANCHORED AT TOP PLATE 7) PROVIDE REVISED ELECTRIC PLAN AND LOAD CALCULATION FOR ADDDED 220 VAC CIRCUITS |