Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date |
Description |
Inspector |
Results |
Comments |
| 09/10/2002 |
EXT METAL CLIPS/EXT SHEATHING |
|
Approved |
IVRS - Inspection 0000* |
| 07/25/2002 |
EXT METAL CLIPS/EXT SHEATHING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) GARAGE SHEARWALL #1 REQUIRES PAHD 42 HOLDOWN SHEARWALL AND DESTROYED BY DOOR 2) PROVIDE ICBO REPORT PFC4354 DETAIL FOR INSTALLATION OF H2.5 CLIPS TO TJI AND DETAIL FOR CONNECTION AT INTERIOR BEARING WALLS. NAILS NOT ALLOWED TO BE DRILLED HORIZONTALLY INTO TJI CHORD. SEVERAL TJI'S HAVE SPLIT CHORDS. PROVIDE ENGINEER CITY OF TUCSON APPROVED REPAIR 3) INTERIOR BEARING WALL NOT FRAMED PER PLAN 4) 01030 NOT ON PERMIT WAS GIVEN A PARTIAL ALSO |