Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/30/2003 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000*ALL CORRECTION HAVE BEEN MADE OK FOR C OF O. | |
01/03/2003 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0935* UNIT #2 STILL NOT FUSED CORRECTLY. HEAT STRIP WAS REMOVED FUSE WERE NOT CHANGED. PAY A REINSPECTION FEE PRIOR TO NEXT INSPECTION OK FOR TEMP C OF O. |
|
01/02/2003 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*1.) DATA PLATE STILL NOT MARKED W/PROPER HEAT KIT. 2.) UNIT #1 OVERFUSED? 3.) ROOF JACK STILL NOT CHANGED UNIT UNIT1 4.) RELOCATE ELEC. DISCONNECT UNIT 1 RECALL FOR INSPECTION. |
|
12/23/2002 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*1.) PROVIDE A ROOF JACK AT LOW VOLTAGE PENETRATION THRU ROOF. 2.) MAKE UNIT DATA PLATE W/PROPER HEAT KIT INSTALLED & FUSE ACCORDINGLY. 3.) #8 WIRE NOT ADEQUATE FOR 60 AMP CIRCUIT FROM ELEC. DISCONNECT TO A/C UNIT. |
|
12/06/2002 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000* OK FOR CEILING TILES. |