Permit: T02CM02734

Parcel: 121016260


Addresses:

1951 N WILMOT RD 05


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T02CM02734

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/30/2003 MECHANICAL - FINAL Approved IVRS - Inspection 0000*ALL CORRECTION HAVE BEEN MADE OK FOR C OF O.
01/03/2003 MECHANICAL - FINAL Denied IVRS - Inspection 0935*
UNIT #2 STILL NOT FUSED CORRECTLY. HEAT STRIP WAS REMOVED FUSE WERE NOT CHANGED.
PAY A REINSPECTION FEE PRIOR TO NEXT INSPECTION OK FOR TEMP C OF O.
01/02/2003 MECHANICAL - FINAL Denied IVRS - Inspection 0999*1.) DATA PLATE STILL NOT MARKED W/PROPER HEAT KIT.
2.) UNIT #1 OVERFUSED?
3.) ROOF JACK STILL NOT CHANGED UNIT UNIT1
4.) RELOCATE ELEC. DISCONNECT UNIT 1
RECALL FOR INSPECTION.
12/23/2002 MECHANICAL - FINAL Denied IVRS - Inspection 0999*1.) PROVIDE A ROOF JACK AT LOW VOLTAGE PENETRATION THRU ROOF.
2.) MAKE UNIT DATA PLATE W/PROPER HEAT KIT INSTALLED & FUSE ACCORDINGLY.
3.) #8 WIRE NOT ADEQUATE FOR 60 AMP CIRCUIT FROM ELEC. DISCONNECT TO A/C UNIT.
12/06/2002 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*
OK FOR CEILING TILES.