Permit: T02CM02720

Parcel: 10706019D

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/07/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
11/06/2002 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*
11/04/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) ALL OUTSIDE LIGHTS TO MEET LIGHTING CODES SECTION #5. 2.) COUNTER TOP RECEPTICALES IN KITCHEN TO BE GFCI PROTECTED 3.) SUPPORT NM CABLE TO & BETWEEN LIGHTS (KITCHEN) 4.) PLEASE FULLY TERMANATE CONDUCTORS UNDER SCREWS 5.) IF MORE THAN 1/8" BETWEEN BOX SURFACE AND DEVICE AN APPROVED EXTENDER RING IS NEEDED METAL IS NOT APPROVED. 6.) PRTECT CONDUCTORS FROM SHARP METAL EDGES HALL FIXTURES.
10/24/2002 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*OK FINAL