Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/19/2002 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000*PLEASE SUPPORT NM CABLES ABOVE PANELS. | |
| 08/15/2002 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999*1.) USE A APPROVED CONNECTORS FOR NM CABLE 2.) WE HAVE AN EXPOSED NM CABLE ABOVE PANEL ISA 3.) PLEASE STRAP NM CABLE WITH IN 12" OF BOXES. 4.) PROVIDE FHA STRAPS TO PROTECT NM CABLE 300-4. 5.) MAINTAIN FIRE WALL SEPERATION 300-21. 6.) PLEASE REVISE PERMIT & PLAN TO EN COMPASS ALL WORK UNDER CONSTRUCTION. 7.) WHERE IS PAGE E-1 OF PLANS. |
|
| 07/08/2002 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000*FIRE DAMAGE TO PANEL FEEDERS, PANELS BRANCH CIRCUITS, (ROMEX) DAMAGED BY FIRE THE ENTIRE WEST WING, 2ND FLOOR NEED TO REPLACE ALL CORRIDOR WIRING, CHECK OUT AC SYSTEM, DO NOT COVER WALLS PRIOR TO APPROVAL OF NEW INSTALLATION, FIRST FLOOR WEST WING APPEARS TO BE MOSTLY WATER DAMAGE. |