Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
08/08/2003 PLUMBING - INTERMEDIATE Approved IVRS - Inspection 0000*/ 1) PLUMBER TO COMPLETE ODDS AND ENDS ON LAVATORIES 2) OK TO COVER ALL AREAS ON ALLL FLOOR S3) CALL EIN ROOF DRAINS 03037 OR 03035 INTERMEDIATES WHEN READY
06/16/2003 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) 3" AND 2 1/2" COPPER SERVICE UP TO FIFTH FLOOR
06/08/2003 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) OVERHEAD COPPER ON GROUND FLOOR AS HIGHLIGHTED ON PLAN-OK 3" REMAINING
06/03/2003 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) 2 BREAKROOM SINKS 3RD FLOOR W/COPPER IN THE CORRIDOR EAST TO TIE IN AT MAIN OK TO COVER 2) 2 BREAKROOMS SINKS ICE MAKER ON 2ND FLOOR BACK TO MAIN OK-OK TO OVEN
06/01/2003 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
05/30/2003 PLUMBING - INTERMEDIATE Partial Approval 1) FOURTH FLOOR GREAT ROOM SINK WATER PIPING ???UP AND INTO CORRIDOR OK. PRESSURE TEST OK. OK TO COVER.
05/13/2003 PLUMBING - INTERMEDIATE Partial Approval BATHROOM GROUPS 2ND 3RD & 4TH FLOOR AS HIGHLIGHTED ON PLAN OK
WATER TEST OK.
05/09/2003 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection 0000*VENT UP ALONG COLUMN #7-B OK
WATER TEST OK
2.) DRAINAGE PIPING OK AS HIGHLIGHTED ON PLAN OK.
04/18/2003 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
1.) UNDERSLAB COMPLETE.
2.) INTERMEDIATE AS HIGHLIGHTED ON PLAN.
04/14/2003 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection 0000*DWV ALONG 3 @ INCLUDING SECOND FLOOR BREAK ROOM SINK AND REVENT ON THIRD FLOOR OK.
OK TO COVER.
04/13/2003 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection 0000*1.) DWV PIPING AT C-3 RISERS AND WASTE NEED TO SEE SECOND FLOOR VENT UNDER TEST.
2.) OK ALL FLOORS (EXCEPT TWO).
04/10/2003 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection 0000*4-2" water services and one three inch service under slab. ok sil-phos 90 ok ok for concrete.
04/08/2003 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
1.) 4" X 2" N/H SANTEE REPLACED WITH 4" N/H SANTEE W/4" X 2" RED OK.
2.) CONTINUING COLUMN "B" 3.5 FROM THIRD FLOOR UP TO FIFTEEN. FLOOR OK WATER TEST OK.
OK TO COVER.
04/07/2003 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
COLUMNS 'B' 3.5 MOPSINKS AND 3RD FLOOR BREAKROOM SINK N/H DWV FIRST SECOND, UP TO THIRD FLOOR OK.
WATER TEST OK
CHANGE 4"X2" COMBO ABOVE 2ND FLOOR TO 4" SANTEE W/ 4"X2" RED AS PER PLAN.