Permit: T02CM02717

Parcel: 124041000


Addresses:

845 N PARK AV


Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T02CM02717

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
04/18/2003 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection 0000*
03/27/2003 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection 0000* 1) N/H FOR FS-2 ( 6") AND 6'' RISER FOR ABOVE OK. OK TO COVER UNDERGROUND
02/21/2003 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection 0000*1ST FLOOR 1-P-208 TEST OK SEC PLAN.
1ST FLOOR STACK 2 P-208 TEST OK
AND 4" BRANCH FOR FIXTURE.
02/20/2003 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection 0000*1.) UNDERGROUND FOR BATHROOM GRID 3-4/C.C.S OK
2.) 3 EACH 4" STUBS 10' LONG FOR FUTURE GREASE INTERCEPTORS ON LINE 8.
3.) 4" WASTE LINE C 2.2.-3.
02/12/2003 PLUMBING - ROUGH, SOIL Partial Approval 1.) 6" DIP FROM 2 WAY CLEAN OUT TO MAN HOLE OK WATER TEST OK
OK TO COVER.
02/11/2003 PLUMBING - ROUGH, SOIL Partial Approval 1.) AS HIGHLIGHTED ON PLAN OK TO COVER.
01/24/2003 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection 0000*6" N/H DWV AS NOTED ON PLUMBERS PLAN OK TO COVER.
01/21/2003 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection 0000*/ 1) 6" WATER HEATER UNDERGROUND AS HIGLIGHTED ON PLUMBERS PLAN 2) WATER TEST OK 3) OK TO COVER THIS AREA