Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T02CM02711
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/25/2003 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection 0000*OK FOR SHEET ROCK. | |
03/13/2003 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection 0999* 1.) INSULATE BARE METAL ON TAPERED REGISTER BOXES. USE INSULATION ON TWYES NOT TAPED. 2.) CRIMP ON DRYER VENT ELBOWS RESTRICTING SIZE OF DRYER VENT. 4" ROUND VENT PIPE DOES NOT FIT IN A 3 1/2" WALL. RECOMMEND USING 3 X 4 DOWNSPOUT. 3.) REMOVE SCREEN FROM DRYER VENT T-TOPS. 4.) PROVIDE NAIL PLATES ON DRYER VENTS AS NEEDED. 5.) PROVIDE BACKING AROUND CEILING BOXES. 6.) UNIT 15 MISSING RETURN AIR. |