Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 07/23/2002 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 07/22/2002 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) NEED WATER TEST ON SEWER LINE ONLY 2) FRAMING OK |
| 07/19/2002 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) NEED WATER TEST ON SEWER AND DRAIN PIPING 2) CONDENSATE LINE NOT INSTALLED FOR A/C 3) FRAMING WITHELD UNTIL ALL OTHER CORRECTED |
| 07/10/2002 |
FRAMING |
|
Not ready for Inspection |
IVRS - Inspection 0000* |