Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 11/19/2002 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 11/08/2002 |
FRAMING |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) FROM LAST INSPECTION NAIL ALL PERIMETERS, EXTERIOR SHEATHING SHEAR # SW2 AT N/W WALL WEST OF DOOR TOP NAILING AT BLKS 2) SHEAR WALLS #SW1 AND SW2 REQUIRE 5/8" DIAMETER BOLTS AT 48" ON CENTER SEE SHEAR SCHEDULE 3) FROM LAST INSPECTION UNDERGROUND CHASE FOR GAS TO BE INSTALLED PER DRAWING LEFT ON SITE, IF YOU WANT TO LEAVE AS IS GIVE ME A STAMPED APPROVED DETAIL 4) MOVE ALL PEX 12" AWAY FROM CAN LIGHTS 5) FROSTED WINDOW COVERED WITH NEW WALL OLD BATH REQUIRES EXHAUST FAN 6) WHAT IS GALVANIZED 3/4" PIPE WITH CAP? NEXT TO NEW SINK? 7) LOCATE BASE BOARD HEATERS 8) CAPPED OFF GAS LINE IN CEILING, NEEDS A EXPOSED SHUT OFF VALVE TWO TOTAL 9) GAS SUPPLYED FROM WHERE? 10) CHECK OVER HANG AT KITCHEN ISLAND, NO OUTLETS UNDER COUNTER IF PROJECTS MORE THAN 6", PONY WALL NOT INSTALLED YET |
| 10/11/2002 |
FRAMING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) PATIO GIRDER POSTS AND ENTRY (N.W.) NOT IN YET CONNECTION |