Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE RELOCATION
Permit Number - T02CM02679
Inspection Description - ELECTRIC - SERVICE RELOCATION
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/06/2002 | ELECTRIC - SERVICE RELOCATION | Approved | IVRS - Inspection 0000*FINISH ALL ID ON SWITCHES & DISCONNECT 2.) PROVIDE LISTING ON REDUCTION & INDUCTION EQUIPMENT FOR FINAL REDUCTION EQUIPMENT TO BE INSTALLED 3.) EXISTING GUTTER RESET GROUND LUG TO CONTACT FULL SURFACE. 4.) RIM JUMPER FROM GROUND LUG TO GUTTER BOX. BODY AT VAC DIS'S 6.) CORD FOR VAC PUMP CONNECT GET OK FROM ENG. IF NOT EXTRA HARD USAGE. 6.) LISTING ON VAC PUMP & CONTROL CABINETS REQUIRED CALLF OR FINAL ONCE ALL EQUIPMENT INSTALLED. |