Permit: T02CM02674


Addresses:

1021 N WILMOT RD


Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T02CM02674

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
08/26/2002 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection 0000*1.) SOIL WATER TEST IS OK 2.) OK TO BACKFILL TRENCH. 3.) NOTE ALL FITTING HAVE HAD A WATER TEST WITH 10' HEAD. 4.) AIR PRESSURE TEST FOR C.W. INTO PAD IS OK.
08/21/2002 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection 0000*1.) SOIL WATER TEST IS OK 2.) YARD WATER LINE FROM METER TO SOUTH WEST CORNER OF BLDG. IS OK 3.) NOTE: THIS INSPECTION IS FOR ROUGH PLBG. AND IS NOTED ON APPROVED PLAN 4.) OK TO BACKFILL TRENCH. 5.) HCS CONNECTION & SITE SEWER IS OK TO BACKFILL.