Permit: T02CM02663

Parcel: 12308007C

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T02CM02663

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
07/31/2002 PLUMBING - ROUGH, SOIL Approved
07/22/2002 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection 0999*1.) CAN NOT CONNECT A WASTE LINE INTO A VENT ON 1 1/2" WASTE FOR P-3. 2.) RE TEST SYSTEM. 3.) ST SAW TEE HAS LEAK @ 3 X 2 BUSH REMOVE THIS FITTINGS.
07/12/2002 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection 0999*1.) CAN NOT HAVE COUPLING WITHIN THE STRUCTURE. 2.) APPROVAL PLAN DOES NOT SHOW AUTO WASHER BOX AND LAUNDRY SINK. WILL REQUIRE A REVISED & APPROVED DRAWING SHOWING THIS PLAN CHANGE. 3.) MUST PROVIDE WATER TEST ON WASTE VENT SYSTEM. 4.) CAN NOT MAKE P.O.C. OF NEW BLDG 1 1/2 DRAIN INTO TRAP ARM FOR EXSISTING LAVATORY. 5.) CAN NOT EXCEED 135' OF CHANGE OF DIRECTION ON 1 1/2 " HORIZONTAL WASTE WITHOUT PROVIDE A C.O. 6.) MUST VERIFY PLBG. CONTRACTOR LICENSE @ TIME OF NEXT INSPECTION 7.) A WASHER BOX TRAP ARM MUST HAVE MIN TRAP ARM DISTANCE.