Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T02CM02663
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/09/2002 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* APEX ELECTRIC DOING WORK. | |
07/01/2002 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0245*INSTALL GROUND SCREWS OR GROUND PIGTAILS EACH DEVICE BOX. PER ART 250 NEC. 2.) BENDING RADIUS OF MC NOT TO EXCEED 7 TIMES THE DIA OF CABLE 334- NEC. 3.) MUST HAVE 6" FREE CONDUCTOR LENGTH AT DEVICE BOXES PER 300-14 NEC. 4.) NEED VERIFICATION OF L-11 LICENSED CONTR. DOING WORK. NAME & PH# PLEASE. |