Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T02CM02644
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/20/2002 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000* | |
08/16/2002 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*DO NOT ATTACH DUCT HANGERS/STRAPS FOR EXHAUST DUCT TO SUPPLY DUCT ABOVE. THIS IS NOT ACCEPTABLE. REMOVE STRAPS SEAL HOLES IN SUPPLY DUCT AS NECESSARY. SUPPORT EXHAUST DUCT USING ACCEPTED METHODS. | |
08/13/2002 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000*AREA ABOVE CEILING GRID & TILES IS RETURN AIR PLENIUM EXHAUST DUCTS IN PLENIUMS MUST BE RIDGID MTL. W/SEALED JOINTS APPROVED PLAN CALLS FOR EXHAUSTING INTO WALLS EXHAUST DUCT. DUCT AS TERMINATED MAY EXHAUST POLISH INTO MALL ENTRNACE. NOTE! THESE FUMES HAVE BEEN VERY POTENT AND DO GENERATE COMPLIANTS FROM SURROUNDING TENANTS IF FUMES ARE OBJECTIONABLE. 2.) CONDENSATE FROM EXISTING AIR HANDLER IMPROPER TERMINATION FOR OVER FLOW. PRIMARY & SECONDARY (OVERFLOW) CANNOT TERMINATE INTO SOME WASTE LINE. |