Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/13/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 08/08/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*1.) PLEASE TIGHTEN FITTINGS AT WATER HEATER. 2.) MAIN BREAKER TO HAVE A HOLD DOWN DEVICE AS APPROVED BY MANFACTURE 384-16. 3.) PLEASE APPLY TAP RULES AS PER ARTICLE 240. 4.) USE APPROVED TYING METHODS FOR ELECTRICAL. THAN IS NOT APPROVED. 5.) JUNCTION BOXES ABOVE CEILING TO BE SUPPORTED 6.) EXIT SING BY REAR DOOR NOT WORKING. |