Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 08/20/2002 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 08/16/2002 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) PROVIDE 2 X BRACING AT MIDSPAN OF DIAGONAL BRACES PER DT1/6 AT BOTH ENDS OF BUILDING 2) TOE NAIL BOTTOM CHORD OF INTERIOR SHEAR TRUSS TO TOP PLATE PER DT1/10 16D'S 12" ON CENTER 3) NEED TO COMPLETE MESHA INSTALLATION AND STAPLING AND CAULKING AROUND ALL PROTRUSIONS 4) PROVIDE PROPER CLEARANCE FROM COMBUSTIBLES FOR KITHCEN COOKING UNIT |