Permit: T02CM02637

Parcel: 123172450


Addresses:

1440 E LEE ST #01

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/15/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*1.) USE AN APPROVED FITTING AT L.B. ALSO CANNOT INSTALL ROMEX IN A COMPLETE RACEWAY SYSTEM. 2.) CORRECTLY IDENTIFY ON GROUNDED CONDUCTORS CK ON FINAL FOR 1422 E LEE. CLOSET FIXTURES NOT INSTALLED AT THIS TIME.
10/14/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
10/07/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1.) BATH FIXTURE IS REQUIRED TO HAVE A BOX AND GROUND FIXTURE. 2.) TIGHTEN WATER HEATER CONNECTOR AND SUPPORT FLEX CONDUIT. 3.) EXTENDER RINGS ARE NEEDED WHERE MORE THAN 1/8" BETWEEN BOX & DEVICE. 4.) CONDUCTOR TO BE INSTALLED IN A CLOCK WISE DIRECTION UNDER SCREWS. ALSO TIGHTEN CONDUCTOR SCREWS. 5.) MISSING FIXTURE IN CLOSET. 6.) INSTALL GROUND AT SUBPANEL CORRECTLY. 7.) A DISCONNECTING IS REQUIRED FOR WATER HEATER. 8.) MISSING FACE PLATES & DEVICES 9.) SUPPORT CONDUIT ACCROSS ROOF AND SEALTITE. 10.) TIGHTEN ALL FITTING CONDUIT & SEALTITE. 11.) FUSE TOO LARGE FOR CONDUCTORS. 12.) FILL ALL UNUSED OPENINGS.
10/04/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*WH. USE CORRECT CONNECTOR & TIGHTEN CONNECTOR AT J-BOX 2.) INTERMINATE CONDUCTOR IN PANEL AC'S & 10 CIR 3.) PANEL NEED TO BE SCHEDULED PROPERLY TIE IN CONDUCTORS TO REMAIN IN PANEL. 4.) NEED PLAN ON SITE 5.) NEED ACCESS TO ROOF. 6.) PANEL SCHEDULE MISSING.