Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY SERVICE
| Date |
Description |
Inspector |
Results |
Comments |
| 10/02/2002 |
ELECTRIC - TEMPORARY SERVICE |
|
Approved |
IVRS - Inspection 0000*SENT TEP ON 10/3/02 AT 9:15AM. |
| 10/01/2002 |
ELECTRIC - TEMPORARY SERVICE |
|
Denied |
IVRS - Inspection 0999*1.) USE ANTIOXIDE COMPOUND ON ALUMINIUM CONDUCTORS 2.) BONDING DEVICES ARE NEEDED ON NIPPLES IN GUTTER. |
| 09/26/2002 |
ELECTRIC - TEMPORARY SERVICE |
|
Partial Approval |
IVRS - Inspection 0000*1.) FILL UNUSED OPENINGS IN PANEL 2.) A PERMANENT METAL ADDRESS LABEL IS NEEDED. |