Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/14/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* / 1) OK FOR FINAL 2) SENT TO TEP 7/15AM |
| 07/10/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* 1) WHERE IS DISCONNECTING MEANS FOR GARAGE DOOR MOTORS 2) SUPPORT CONDUIT AS PER CODE. 3) FILL UNUSED OPENING IN BOXES 4) APPROVED EXTENDER RUGS ARE NEEDED WHERE MORE THAN 1/4'' FROM BOXES TO SURFACE 370-20. 5) PLEASE BOND DISCONNECT ENCLOSURE 6) SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING 250-8 |