Permit: T02CM02563

Parcel: 133201280


Addresses:

602 N WILMOT RD


Inspection Status: Approved

Inspection History: REINFORCED MASONRY PRE-GROUT

Permit Number - T02CM02563

Inspection Description - REINFORCED MASONRY PRE-GROUT

Inspection Status - Approved

Date Description Inspector Results Comments
07/28/2003 REINFORCED MASONRY PRE-GROUT Approved
03/26/2003 REINFORCED MASONRY PRE-GROUT Partial Approval
01/31/2003 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection 0000*
01/29/2003 REINFORCED MASONRY PRE-GROUT Not ready for Inspection IVRS - Inspection 0000*
01/28/2003 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection 0000*OK TOP OUT GROUT WEST WALL GRID LINE 5 TO 3 L TO N.
01/27/2003 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection 0000*3RD LIFT, FINISH BOND BEAM WORK.
01/23/2003 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection 0000*2nd lift on elec. room, and final lift grid line 4 L-K.
01/22/2003 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection 0000*
01/21/2003 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection 0000*OK TO 8' @ CHANGING RM.
OK TO 8' AT MECH RM.
01/15/2003 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection 0000*1.) LINE 6 C-K TOP OUT.
GET RFI FIX FROM ENGINEER CONCEPTING COLUMN @ L-3.9.
BARS FOR COL. NOT INSTALLED PER KEYNOTE 21/51.2 BARS HAVE BEEN BUNDELED AND PLACED PARALLEL TO FACE RATHER THAN PERPENDICULAR.
01/13/2003 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection 0000*GRID 6-4 @ C TO K.
01/07/2003 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection 0000*OK TO 8' SOUTH WALL BLDG B
OK TO 12' NORTH WALL.
01/03/2003 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection 0000*
OK 4' ON BLDG B WEST & EAST WALLS.
OK 8' ON NORTH WALL.
12/27/2002 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection 0000*1ST LIFT OK TO PROCEEDS.
12/26/2002 REINFORCED MASONRY PRE-GROUT Denied IVRS - Inspection 0999*
12/19/2002 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection 0000*
12/02/2002 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection 0000*