Inspection Status: Partial Approval
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 08/11/2003 |
FRAMING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) PARTIAL ON FRAMING PENDING BEAM AT PENETRATION TO EXISTING |
| 08/08/2003 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) TRAP ON LAUNDRY RISER MUST BE BETWEEN 18"-30" BELOW INLET 2) FRAMING WITHELD FOR PLB CORRECTIONS |
| 07/31/2003 |
FRAMING |
|
Denied |
IVRS - Inspection 0160*/ 1) SHOW LP1225 AT FLOOR FRAMING 2) FIRE STOP SOFFITS AND DROPS 3) FRAME AT TRANSITION WALL BEAM NOT COMPLETED 4) SHIM HEADERS 5) PROVIDE PORCH DETAIL 6) PROVIDE U-VALUE 7) GROUND ALL STEEL BOXES 8) PROTECT CONDUCTORS AT SHARP EDGES 9) GROUND MAIN SERVICE-2 RODS AT 6' SEPARATION 10) LAUNDRY VENTING INCORRECT 11) PROVIDE WATER LINE AND WASTE TEST 12) NAIL PLATE WASTE LINES 13) NOTE MECHANICAL NOT COMPLETED |