Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY SERVICE
| Date |
Description |
Inspector |
Results |
Comments |
| 10/14/2002 |
ELECTRIC - TEMPORARY SERVICE |
|
Approved |
IVRS - Inspection 0000* |
| 09/11/2002 |
ELECTRIC - TEMPORARY SERVICE |
|
Denied |
IVRS - Inspection 0230*/ 1) UFER GROUND WAS NOT INSPECTED. INSTALL 2 EACH 8 FOOT GROUND RODS AT LEAST 6 FEET APART CONNECTED TO SERVICE PANEL WITH A CONTINOUS #4 CONDUCTOR 2) YOU MUST CALL FOR EXCAVATION AND LAYOUT AS WELL AS PRE-SLAB INSPECTIONS WHEN YOU HAVE CORRECTED SITE PLAN |