Permit: T02CM02510

Parcel: 12105018C


Addresses:

5550 E HAMPTON ST

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
06/27/2002 PLUMBING - INTERMEDIATE Approved IVRS - Inspection 0000*1.) WASTE & VENT SYSTEM IS OK 2.) OVERHEAD WATER DISTRIBUTION I SOK 3.) OK FOR DRYWALL.
06/26/2002 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*1.) WORK COVERED BEFORE INSPECTION 2.) HORIZONTAL VENT REQUIRES SUPPORT 3.) WATER TEST OK.
06/25/2002 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*1.) MUST PROVIDE WATER TEST ON SYSTEM WASTE & VENT ALL THE WAY TO TOP OF VENT THRU ROOF. 2.) PLUMBERS TAPE SI NOT APPROVAL MATERIAL FOR HANGING HORIZONTAL VENT PIPE MUST USE APPROVED HANGERS OR STRAP. 3.) 1 1/2" HORIZONTAL VENT HAS EXCEEDED MAXIMUM ALLOWABLE DISTANCE. SEE TABLE 7.5 94 UPC.