Permit: T02CM02510

Parcel: 12105018C


Addresses:

5550 E HAMPTON ST

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
06/19/2002 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection 0000*1.) ALL CORRECTIONS HAVE BEEN MADE.
06/18/2002 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection 0999*CAN NOT HAVE A FERNED COUPLING WITHIN THE STRUCTURE. MUST HAVE A SHIELDED OR SOLID WELD COUPLING. 2.) OK TO CONCRETE UP TO P.O.C. OF NEW BLDG. DRAIN DO NOT COVER P.O.C.
06/17/2002 PLUMBING - ROUGH, SOIL Denied 1.) CAN NOT USE A FLAT FACED BUSHING ON HORIZONTAL DRAINAGE SEE SECTION: 311.5 94 UPC INTERPETATIONS USE BELL REQ. 2.) MUST USE CAST IRON BLIND CAPS FOR PERM CAPS ON CAST IRON WASTE. 3.) REMOVE 3X2 LOW HEEL 1/4 BEND AND REPLACE WITH 1/4 BEND FOR 3" EXISTING WASTE. 4.) SOIL WATER TEST IS OK.