Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE RELOCATION
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/19/2003 | ELECTRIC - SERVICE RELOCATION | Approved | IVRS - Inspection 0000*SENT TO TEP ON 3/20/03 AT 9:15AM OK TO CLEAR RELOCATED SERVICE OK CABLE DROP. | |
| 03/14/2003 | ELECTRIC - SERVICE RELOCATION | Partial Approval | IVRS - Inspection 0000*BOTH TRANS GROUNDED TO RODS & WATER BOND. MAIN 200A BONDED TO WATER OK SUBJECT TO LETTER FROM ENGINEER. 1.) DO NOT HAVE RECORD OF SW GEAR INSPECTION. 2.) WILL NEED ENG APPROV ON GROUNDING FOR TRANSFORMERS. 3.) FOR TEMP SER LABEL ALL DISCONNECTS AND CIR'S 4.) INSTALL FUSES AT SW GREAR AND IN BLDG. |
|
| 02/21/2003 | ELECTRIC - SERVICE RELOCATION | Partial Approval | IVRS - Inspection 0000*1.) PLEASE HAVE ELECTRICAL ENGINEER TO INDICATE METHOD FOR BONDING WATER PIPING TO ELECTRICAL EQUIP. AND NEW SERVICE, TO COMPLY WITH ART 250-104 NEC. | |
| 02/20/2003 | ELECTRIC - SERVICE RELOCATION | Not ready for Inspection | IVRS - Inspection 0000* | |
| 02/19/2003 | ELECTRIC - SERVICE RELOCATION | Not ready for Inspection | IVRS - Inspection 0000* | |
| 01/29/2003 | ELECTRIC - SERVICE RELOCATION | Partial Approval | IVRS - Inspection 0000* |