Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 07/08/2002 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 06/25/2002 |
FRAMING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) STAIR DETAIL 2) DETAIL 25 S1.2 NOT PER PLAN 3) LEAVE BOTH AREAS EXPOSED |
| 06/24/2002 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) HD 14A UNDER STAIRS NUTS NOT INSTALLED LEFT AND RIGHT 2) SW9 SHEAR NOT NAILED PER SCHEDULE 3) FIRE BLOCK AT STAIRS 4) BLOCK ALL REGISTERS 3 SIDES 5) EXHAUST FAN AT MASTER TOILET NOT WIRED 6) DETAIL FOR UNDER STAIRS LEDGER 7) FIREBLOCK CHASE AT FRONT BEDROOM 2ND FLOOR 8) ROMEX SHEATHING MUST TERMINATE INSIDE PANEL 9) DWV'S FAILED WATER TEST 10) PLUMBERS TAPE NOT ALLOWED TO SUPPORT PLUMBING 11) LADDER BACKS NOT ALLOWED AT SHEARWALLS |