Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T02CM02466
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/23/2002 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection 0000* | |
| 09/11/2002 | PLUMBING - ROUGH, SOIL | Partial Approval | 1.) T & P RELIEF FROM SECOND FLOOR REROUTED TO JANITOR SINK. 2.) CLOSET FLANGES OK 3.) SUMP OK OK TO COVER.4.) NEED TO SEE FINAL CONNECTION OF SUMP DRAIN TO EXISTING | |
| 07/31/2002 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection 0000*1.)N/H DWV UNDERGROUND O TO FIVE FEET PAST JANITOR SINK 2.) WATER TEST ONE TEN FOOT RISER OK 3.) OK TO BACKFILL 4.) NEED TO SEE FINAL CONNECTIONS UNDER SLAB. | |
| 07/29/2002 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection 0999* 1.) NO WATER TEST 2.) J.S. TRAP ARM BACKPTICHED 3.) DRAINAGE PIPING REQUIRES 2% PITCH. 4.) REPAIR LEAK IN ABANDONED OVER HEAD DRAIN LINE. 5.) IS UNDERGROUND COPPER TYPE "K"? | |
| 07/25/2002 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection 0999*NOT INSTALLED PER APPROVED PLAN. |