Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date |
Description |
Inspector |
Results |
Comments |
| 09/23/2002 |
PLUMBING - ROUGH, SOIL |
|
Approved |
IVRS - Inspection 0000* |
| 09/11/2002 |
PLUMBING - ROUGH, SOIL |
|
Partial Approval |
1.) T & P RELIEF FROM SECOND FLOOR REROUTED TO JANITOR SINK. 2.) CLOSET FLANGES OK 3.) SUMP OK OK TO COVER.4.) NEED TO SEE FINAL CONNECTION OF SUMP DRAIN TO EXISTING |
| 07/31/2002 |
PLUMBING - ROUGH, SOIL |
|
Partial Approval |
IVRS - Inspection 0000*1.)N/H DWV UNDERGROUND O TO FIVE FEET PAST JANITOR SINK 2.) WATER TEST ONE TEN FOOT RISER OK 3.) OK TO BACKFILL 4.) NEED TO SEE FINAL CONNECTIONS UNDER SLAB. |
| 07/29/2002 |
PLUMBING - ROUGH, SOIL |
|
Denied |
IVRS - Inspection 0999* 1.) NO WATER TEST 2.) J.S. TRAP ARM BACKPTICHED 3.) DRAINAGE PIPING REQUIRES 2% PITCH. 4.) REPAIR LEAK IN ABANDONED OVER HEAD DRAIN LINE. 5.) IS UNDERGROUND COPPER TYPE "K"? |
| 07/25/2002 |
PLUMBING - ROUGH, SOIL |
|
Denied |
IVRS - Inspection 0999*NOT INSTALLED PER APPROVED PLAN. |