Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/12/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*FINAL APPROVED.
08/29/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) GROUND LUGS SCAPE & BOLT NO TEC SCREWS. 2.o STRAP ALL 1 1/2" CONDUITS. 3.) PHASE ID 480 VOLT COLORS IN METER COMPARTMENT. 4.) SEAL LARGE OPENING IN EQUIPMT. 5.) TY RAP CONDUCTORS TO UNISTRUT IN MAN HOLE. 6.) BELL WIRE IN 480 EQUIPMENT TO BE RATED 40V. VERIFY 7.) ID AT SW GEAR APPAY #1 AND FIELD ARRAY #1 #2.