Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/29/2003 |
BUILDING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 04/25/2003 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) ITEMS 1, 2, AND COOK TOP (5B) FROM 4/17 INSPECTION HAVE NOT BEEN CORRECTED 2) NEXT FAILURE WILL INCUR RE-FEE |
| 04/17/2003 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) NO FUSES AT DISCONNECT FOR CONDENSOR 2) WHAT IS THE 12-30 YELLOW WIRE FOR OUTSIDE MAIN PANEL 3) EXPOSE OR INSTALL BOND CLAMP TO GAS LINE 4) PROVIDE A WATER PROOF COVER FOR GFCI OUSIDE-LIGHTS AND IRRIGATION PLUGGED IN 5) KITCHEN SINK AND COOK TOP NOT INSTALLED 6) PROVIDE LINE AT WATER HEATER MUST BE ALL SOLID THROUGHOUT NO COILS 7) SINGLE WALL FLU MUST HAVE 6" CLEARANCE FROM COMBUSTIBLES 6) SEAL ALL PENETRATIONS IN GARAGE CEILING MECHANICAL AREA 7) OK TO POUR FOOTERS FOR PATIO WALL |
| 04/14/2003 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) PROVIDE ANTI-SIPHON DEVICES FOR HOSE BIBS 2) NO FUSES AT CONDENSOR DISCONNECT 3) PROVIDE OR EXPOSE BONDING CLAMP AT GAS LINE 4) WILL NEED ACCESS TO INTERIOR OF HOUSE 5) WILL NEED A WATER PROOF COVER OVER GFCI FOR IRRIGATION AND LIGHTS |