Permit: T02CM02418

Parcel: 133231650


Addresses:

7220 E ROSEWOOD ST


Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T02CM02418

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
10/11/2002 ELECTRIC - ABOVE CEILING Approved
09/30/2002 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*FINAL APPROVED OF MC CABLING INSTALLED IN LIEU OF CONDUIT RACEWAY PER ELECTRICAL NOTES, SUBJECT TO APPROVAL IN WRITING FROM ARCH. NOTE THAT BRANCH CIRCUIT INCLUDING THE EMERGENCY SYSTEMS INSTALLED IN MC.
09/27/2002 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0245*1.) SUPPORT MC WITHIN 12' EACH TERM, INCLUDING LIGHT FIXTURES WHERE CABLE EXCEEDS 6'. 2.) DO NOT SUPPORT TO OTHER SYSTEMS SUPPORTS. 3.) NEED TO REVIEW WITH CONTR. HOW NEW CIRCUITS RUN TO PANELS, CIRCUITS COMBINED IN EXSISTING RUNS TO COMPLY WITH 300-15. NEC FOR DERATING.
09/26/2002 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0245*1.) MC CABLE OR FLEXABLE CONDUIT NOT ALLOWED TO UTILIZE OTHER CONDUITS FOR SUPPORT, PER 300-11 NEC. 2.) MUST BE SUPPORTED WITHIN 12" EACH TERMINATION AND AT 6' INTERVALS PER 334-10 NEC. ALSO INSULATE CABLES OR COPPER LINES WHERE TOUCHING. EXCEPTION FOR SUPPORTS OF MC ARE 6' OR LESS LENGTHS USED FOR FIXTURE WHIPS.