Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T02CM02418
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/11/2002 | ELECTRIC - ABOVE CEILING | Approved | ||
09/30/2002 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*FINAL APPROVED OF MC CABLING INSTALLED IN LIEU OF CONDUIT RACEWAY PER ELECTRICAL NOTES, SUBJECT TO APPROVAL IN WRITING FROM ARCH. NOTE THAT BRANCH CIRCUIT INCLUDING THE EMERGENCY SYSTEMS INSTALLED IN MC. | |
09/27/2002 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0245*1.) SUPPORT MC WITHIN 12' EACH TERM, INCLUDING LIGHT FIXTURES WHERE CABLE EXCEEDS 6'. 2.) DO NOT SUPPORT TO OTHER SYSTEMS SUPPORTS. 3.) NEED TO REVIEW WITH CONTR. HOW NEW CIRCUITS RUN TO PANELS, CIRCUITS COMBINED IN EXSISTING RUNS TO COMPLY WITH 300-15. NEC FOR DERATING. | |
09/26/2002 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0245*1.) MC CABLE OR FLEXABLE CONDUIT NOT ALLOWED TO UTILIZE OTHER CONDUITS FOR SUPPORT, PER 300-11 NEC. 2.) MUST BE SUPPORTED WITHIN 12" EACH TERMINATION AND AT 6' INTERVALS PER 334-10 NEC. ALSO INSULATE CABLES OR COPPER LINES WHERE TOUCHING. EXCEPTION FOR SUPPORTS OF MC ARE 6' OR LESS LENGTHS USED FOR FIXTURE WHIPS. |