Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T02CM02418
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/23/2002 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000*LIGHT SWITCHES TRIM PLATES & SCREWS TO BE OF NON ELECTRICAL CONDUCTIVE MATERIAL TO PREVENT PERSONAL FROM POSSIBLE CONTACT OF LIVE PARTS. PER RANDY. | |
08/22/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*NOTES INTERMEDIATE APPROVAL SUBJECT TO OFFICE CONSULTATION. 1.) APPROVED MC PER 517-13 TO BE USED ON LIGHT SWITCHES ALSO UNLESS PER EXCEPTION. 2.)EM CIRCUITS TO BE INSTALLED IN NON FLEXABLE RACEWAYS PER 517-30-3C. |