Permit: T02CM02391

Parcel: 11106403D


Addresses:

3347 E GLENN ST


Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T02CM02391

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
11/06/2002 FRAMING Approved IVRS - Inspection 0000*
10/30/2002 FRAMING Denied IVRS - Inspection 0999* FIREPLACE DRAFT STOP AND SPARK SHIELD NOT INSTALLED .HAVE F/P INSTALLATION MANAGER ON SITE FOR NEXT INSPECTION. ALSO NEXT FAILURE WILL BE CHARGED A RE-INSPECTION FEE
10/28/2002 FRAMING Partial Approval IVRS - Inspection 0000*/ 1) OK TO INSULATE 2) ITEMS 1 FROM 10/22/02 NOT COMPLIED WITH 2) FIREPLACE DRAFT STOP MISSING AT CEILING
10/22/2002 FRAMING Denied IVRS - Inspection 0999*/ 1) CLIP INTERIOR BEARING WALL TO TRUSSES 2) TRIPPLE GIRDER REQUIRES TRIPPLE POSTS EACH END ALSO DOUBLE IN GARAGE 3) FIREPLACE VENT NOT INSTALLED 4) GAS LINE UNDER SIZE FOR BBQ 5) DRAFT STOP K SOFFIT 6) MECHANICAL LOCATION 7) ANCHOR BOLTS LOOSE 8) STRAP TOP PLATES AT BEAM WITH MSTC 28 OR=