Permit: T02CM02388

Parcel: 110091940

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/03/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
12/05/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ 1) ITEMS FROM 9/18/02 NOT COMPLIED WITH SUB PANEL HAS UNDERSIZED GROUND WIRE 2) OVERFILLED CONDUIT ITEM 3 NOT COMPLIED WITH
09/18/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ 1) FROM LAST INSPECTION 30 AMP CIRCUIT TWO HOT WIRES, COLOR CODE WHITE WITH GREEN TAPE 2) 3 20 AMP BLACK WIRES, THREE CIRCUITS, 2 NEUTRALS O GROUND WIRES 3) 100 AMP BACK FED MAIN MUST HAVE A HOLDOWN DEVICE SO IT CANNOT BE REMOVED WITHOUT FIRST REMOVING THE SCREW THAT HOLDS IT TO THE SERVICE EQUIPMENT
09/12/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ 1) 100 AMP BACK FED SERV SQUARE "D" REQUIRES A HOLD DOWN DEVICE 2) CLASSIFIED BRAND BREAKER IS IT APPROVED FOR THIS SQUARE "D" BOX ? NEED LISTING 3) CLEAN UP WIRE PANEL INSIDE IS MESSY 4) 2 POLE 30 AMP BREAKER SUPPLYING DRYER WASHER AND REFRIDGERATOR YOU NEED A BIGGER CIRCUIT 5) MISSING GROUND WIRES FOR NEW CIRCUITS 6) SEAL TITE REQUIRES 4 GRD WIRE 7) ID BY COLOR ALL WIRES IN PANEL
07/15/2002 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*