Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 08/28/2002 |
MECHANICAL - ABOVE CEILING |
|
Approved |
|
| 08/07/2002 |
MECHANICAL - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*INSTALL DUCT SMOKE DETECTORS IN THE RETURN DUCTS NOT THE SUPPLY AS PER 2000 IMC. DUCT SMOKE DETECTORS ARE REQUIRED IN A/C 1 & 2 AS PER SEC 606.2 2000 IMC. OK TO COVER CEILING LEAVE OUT TILE UNDER EACH SMOKE DETECTOR & IN AREA NOT YET COMPLETED. |