Inspection History: ELECTRIC - FINAL
Permit Number - T02CM02380
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/15/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*OK FINAL | |
08/14/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1.) PLEASE VERIFY LISTING USAGE FOR LUGS AND NEUTRAL CONNECTIONS ON 400 AMP SWITCH. 2.) PROVIDE REJECTION PINS AT SERVICE 3.) STACKING OF LUGS IS NOT ALLOWED. 4.) CLEAN SURFACE UNDER LUGS 5.) PLEASE LABEL DISCONNECTS AND SERVICE 6.) FUSES TO E EQUAL TO MANUFACTURES THAT WAS SPECED OUT 7.) SWITCH PLATES TO BE FLUSH WITHOUT A GAP IN BATHROOM 8.) HOOK UP WATER HEATER. 9.) BLANK OFF AL OPEN BOXES. 10.) OUTSIDE LIGHTS TO BE HUNG WITH DIRECTION FROM MANFACTURE. 11.) MAINTAIN WORKING CLEARENCE AT A/C DICONNECTS 110-26. 12.) TIGHTEN FITTINGS 13.) INSTALL ALL STRAND OF CONDUCTOR IN LUG. |