Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 12/02/2002 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 11/01/2002 |
FRAMING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) NO ACCESS TO WATER HEATER 2) ? SERVICE ENT. RISER AND SERVICE MAINS TO LOW |
| 10/22/2002 |
FRAMING |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) CANCEL PER BARB COLLIER 2) TO RESCHEDULE FOR NEXT MONDAY 3) SHE WILL RECALL IN THE INSPECTION REQUEST |
| 06/07/2002 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) FIRE BLOCK CEILING IN BEDROOM CLOSET 2) BARE BULB LIGHT FIXTURES NOT ALLOWED IN CLOSETS 3) LIGHT FIXTURE MUST BE 12" HORIZONTAL FROM CLOTHES IN CLOSET 4) WATER HEATER T&P LINE CANNOT USE CORRIGATED CONNECTOR. SUPPLY OK 5) PROTECT ALL PLASTIC PLUMBING 6) WASHER REQUIRES VENT 7) WATER HEATER T&P MUST EXHAUST DOWN 8) WATER CLOSET VENT MUST EXTEND AT LEAST 6" ABOVE ROOF 9) GROUND METAL ELECTRIC BOXES 10) BATTERY OPERATED SMOKE DETECTORS REQUIRED IN ALL EXISTING BEDROOMS |