Inspection Status: Denied
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 06/19/2002 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) UNTREATED POSTS MUST HAVE 1" SEPARATION BETWEEN WOOD AND CONCRETE |
| 06/12/2002 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) 2 X 6 BEAM ON SOUTH SIDE OF CARPORT INADEQUATE 2) POSTS MUST BEAR UNDER SPLICES OF BEAMS 3) CARPORT ROOF IS FLAT. HAS NO PITCH. PROVIDE PITCH DATA HAVE CARPORT RE-DESIGNED AS A FREE STANDING UNIT |
| 06/10/2002 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) REVISE DRAWINGS TO MATCH AS BUILTS AND GET APPROVAL AT CITY OF TUCSON DEVELOPMENT SERVICES CENTER |
| 06/06/2002 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) JOIST HANGERS REQUIRED EACH SIDE OF FASCIA AS PER DRAWINGS 2) 4 X 6 BEAM CANTELINERS 4' ON EAST SIDE AND 5' ON WEST SIDE MAX PERMITTED IS 24" AS PER APPROVED DRAWINGS 3) EXPOSE OVER HANG AT CARPORT TO VERIFY NAILING AT LEDGER AND REQUIRED JOIST HANGERS 4) 3/8" SLOP PER FOOT REQUIRED AT CARPORT ROOF |