Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date |
Description |
Inspector |
Results |
Comments |
| 07/10/2002 |
EXT METAL CLIPS/EXT SHEATHING |
|
Approved |
IVRS - Inspection 0000* |
| 07/02/2002 |
EXT METAL CLIPS/EXT SHEATHING |
|
Denied |
IVRS - Inspection 0999*/ 1) WEST WALL SHEAR PANELS NOT INSTALLED 2) WALL SHEATHING MUST BE NAILED AT 6" ON CENTER AT ALL SUPPORTED ENDS AND EDGES AND 12" IN FIELD 3) X BRACE 3 TRUSSES ON EACH END FROM RIDGE TO BOTTOM CHORD 4) CLIP GABLE END TRUSS TO TOP PLATES AT 32" ON CENTER |