Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/31/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 07/30/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*1 ABOVE HAS THERE BEEN A GROUNDING SYSTEM OR UFER INSPECTION, INSPECTION OF 7-18-02 APPROVED A #4 COPPER COMING UP OUT OF GROUND SUPPOSED UFER WHICH TIES TO BLDG STEEL AND TO PANEL BUT NOT UFER ITSELF CANNOT FIND UFER SIGN OFF REQUIRED PER 250-32 AS ON PLAN. 2.) PLEASE CALL RAY MAJUTA 791-5550 EXT 1136, |
| 07/29/2002 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*NOT INSTALLED PER PLAN. PLEASE PROVIDE A GROUNDING ELECTRODE SYSTEM FOR A SEPARATE BUILDING. MAIN BREAKER USED IN LIEU OF MAIN DISCONNECT. WILL NEED A MAIN BREAKER RETAINER FOR BACK FED. BREAKER. @ EXTERIOR JUNCTION BOX IT IN REQUIRED TO HAVE A MINIMUM OF SCHEDULE 80 PVC PLEASE MARK CIRCUIT BREAKERS TO GUARD HOUSE. |
| 07/26/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999* |