Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 07/18/2002 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000*OK TO COVER UFER BOND TO STEEL OKAY AND TO PANEL. |
| 07/17/2002 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*NOTES OK WALLS EXCEPT WHERE UFER ENTERS BLD. NOT TIED IN YET, COIL OF #4 BARE NOT TERMINATED, NEED TO INSPECT BOND TO BLD. STEEL AND EQUIP. GROUND BAR IN PANEL. PER 250 NEC. ALSO SEE PLANS. |
| 07/16/2002 |
ELECTRIC - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection 0000* NOTES 1.) COMPLETE ROUGH-IN WALLS P-RINGS, GROUND TAILS IN DEVICE BOXES, 2.) CONDUIT RUNS NOT COMPLETE. |